Description

DP-01-72-100A 3 Phase Voltage and Current Protection Relay 100A

General Informations
In three phase systems, it measures RMS values of AC voltages, currents and system frequency sensitively. Using up direction button (Select) phase-neutral voltages and phase-phase voltages monitor sequentially.
ke-DP01 has many features. Those are;
– Phase Failure (seq)
– Phase Sequence (seq)
– Over Voltage Protection (o – U)
– Under Voltage Protection (u – U)
– Voltage Unbalance (asymmetry) Protection (unb)
– Over Current Protection (o – C)
– Under Current Protection (u – C)
– Current Unbalance (asymmetry) Protection (ubC)
– Over Frequency Protection (o – F)
– Under Frequency Protection (u – F)
When device is turn on if its adjusted voltages and frequency in its
interval and if phase sequence is correct relay switch on.
If any of error occurred ( except phase failure and phase sequence )
at the end of adjusted time relay switch off its contact. When system
return normal values, at the end of time out relay switch on.

Technical Data

3 phase 3P&4W Connection Ok
1 phase 1P&2W connection No
Voltage Ok
Current(A) Ok
Frequency Ok
True RMS Ok
Phase sequnce control Ok
Phase failure Ok
Over Voltage Protection 390-460 V
Under Voltage Protection 300-370 V
Voltage Unbalance Protection %5-%20
Over Current Protection Ok
Under Current Protection Ok
Current unbalance protection %5-%40
Over/Under Frequency protection 40-70 Hz
Error locking (LATCH) function Ok
Current transformer ratio No
2-100A Ok
Relay output 1 adet
Ambient temperature -5 C….+50 C
Storage temperature -20 C….+70 C
Supply voltage 230 Vac<3VA
Dimensions 72x72x80mm
Quantity in 1 box 12