Description

DAM-A-96 AC Universal Ampermeter

General Informations

The device can be used in electrical panels, laboratories, and test devices. Withthe assistance of a current transformer, it measures the AC passingthrough the system in terms of Amper unite. After energizing the device,“dA -A “ message appears on its screen for 2 seconds and then it starts toshow the current value

■ The current transformer ratio can be adjusted between 5/5 and 10000/5 usingthe touch buttons on the front panel of the device.

■ Stores the maximum demand value and the peak value on its memory andkeeps these values even if the energy supply goes off.

■ When the measured value of the seconder current reaches 5,1 A, “ OvEr”the message starts to flash on the screen to warn the user that the value of thecurrent exceeded the limit values.

Technical Data

Relay output current No
Current Ttransformer 5-10000 Ampere Ok
Directly Current Ttransformer 2-100 Ampere No
Over Current Can Be Set No
Under Current Can Be Set No
DEMAND Ok
RS485 – MODBUS RTU RS485, Modbus – Rtu No
Frequency 50-60 Hz
Ambient temperature -5 C….+50 C
Storage temperature -20 C….+70 C
Supply voltage 230 Vac
Dimensions 96x96x56 mm
Quantity in 1 box 12

 

Operational Voltage (Un) : 230Vac

Operating range : (0,8-1,1) x Un

Frequency : 50/60 Hz

Power Consumption : < 4VA

Measurement Sensitivity : %1 +1 digit

Current Transformer

Ratio : 5/5……….10000/5 A

Display : 4 Digits Led Display

Protection Class : IP 20

Terminal Protection Class : IP 00

Operation Temperature : – 5 °C …. + 50 °C

Operation Humidity : %15 …… %95

(without consensation)

Installation : to the panel tap

Dimensions :DAM – A – 96 ( 96x96x80 mm)

: DAM – A – 72 ( 72x72x80 mm)

: DAM – A – 48 ( 48x48x50 mm)