Description
DAM-A-72 AC Universal Ampermeter

General Informations
The device can be used in electrical panels, laboratories, and test devices. Withthe assistance of a current transformer, it measures the AC passingthrough the system in terms of Amper unite. After energizing the device“dA -A “ message appears on its screen for 2 seconds and then it starts toshow the current value
■ The current transformer ratio can be adjusted between 5/5 and 10000/5 usingthe touch buttons on the front panel of the device.
■ Stores the maximum demand value and the peak value on its memory andkeeps these values even if the energy supply goes off.
■ When the measured value of the seconder current reaches 5,1 A, “ OvEr”the message starts to flash on the screen to warn the user that the value of thecurrent exceeded the limit values.
Technical Data
Relay output |
No |
Current Ttransformer 5-10000 Ampere |
Ok |
Directly Current Ttransformer 2-100 Ampere |
No |
Over Current Can Be Set |
No |
Under Current Can Be Set |
No |
DEMAND |
Ok |
RS485 – MODBUS RTU RS485, Modbus – Rtu |
No |
Frequency |
50-60 Hz |
Ambient temperature |
-5 C….+50 C |
Storage temperature |
-20 C….+70 C |
Supply voltage |
230 Vac |
Dimensions |
72x72x80 mm |
Quantity in 1 box |
10 |
Operational Voltage (Un) : 230Vac
Operating range : (0,8-1,1) x Un
Frequency : 50/60 Hz
Power Consumption : < 4VA
Measurement Sensitivity : %1 +1 digit
Current Transformer
Ratio : 5/5……….10000/5 A
Display : 4 Digits Led Display
Protection Class : IP 20
Terminal Protection Class : IP 00
Operation Temperature : – 5 °C …. + 50 °C
Operation Humidity : %15 …… %95
(without consensation)
Installation : to the panel tap
Dimensions :DAM – A – 96 ( 96x96x80 mm)
: DAM – A – 72 ( 72x72x80 mm)
: DAM – A – 48 ( 48x48x50 mm)